MENU
  1. Testing
  2. Fire testing
  3. Single-flame source test

Fire tests

Test apparatus corresponds to standard EN ISO 11925-2. Test results of the building structure can be classified according to standard 13501-1. The dimensions of the test specimens shall be (250 ) mm long by (90 ) mm wide.
450-tilted burner is advanced horizontally until the flame (length 20 mm) reaches the pre-set contact point with the test specimen. Tests may need to be conducted to either surface exposure or edge exposure, or both. The flame application time is 15 or 30 seconds as required by sponsor.

During the test following is recorded: whether ignition occurs; whether the flame tip reaches 150 mm above the flame application point, and the time at which this occurs; whether ignition of the filter paper occurs; observations of physical behavior of the test specimen.

Please contact us

Fred Haas

Head of the Fire testing laboratory
Mobile Phone: +372 53095962

+372 637 9306
Fax: +372 637 9601

test@tuev-nord.ee

We use cookies to optimize the functionality of the website and for web analysis. If you use our website, you agree.